KFU8-FSSP-1D, PEPPERL+FUCHS, Frequency Voltage / Current Converter.
KFU8-FSSP-1D, PEPPERL+FUCHS, Frequency Voltage / Current Converter.

Share:


KFU8-FSSP-1D, PEPPERL+FUCHS, Frequency Voltage / Current Converter.

  • Manufacturer : Pepperl+Fuchs

  • Product No. : KFU8-FSSP-1.D-Y180599

  • Product type : Frequency voltage current converter KFU8-FSSP-1.D-Y180599

  • Limit frequency 40 kHz

  • Voltage or current ouptput

  • Incrementing output

  • (Spacing factor 1 ... 9999)

  • 2-, 3-, 4-wire sensors and rotary encoder can be connected

  • Auxiliary power output for sensors
     

  • Connection via Power Rail

  • Period measurement

  • Display: Input in Hz or 1/min, output in V or mA

  • adjustable updating of indication (0,001 ... 2,5 s)

  • Frequency voltage current converter
    40 kHz version

  • Functional safety related parameters

  • MTTFd : 100 a

  • Supply

  • Rated voltage : 20 ... 30 V DC

  • Fusing : external fusing 4 A

  • Power consumption : < 5 W

  • Indicators/operating means

  • Type : 4-digit, 7-segment red display, 7 mm digit height

  • Display interval : 0.002 ... 9999 Hz or
    0.01 ... 9999 min-1

  • Parameter assignment : keypad-driven menu

  • Input 2

  • Switching point : high: 16 ... 30 V DC; max.10 mA; Ri ? 3 kOhm
    low: 0 ... 6 V DC

  • Connection : terminals 7+, 13- sensor supply
    terminals 14, 15 NPN/PNP input (galvanically isolated)

  • Connectable sensor types : 2-, 3-, or 4-wire proximity switches and incremental rotary encoder

  • Sensor supply : Rated voltage - 1.5 V non-stabilised; = 30 mA short-circuit protected

  • Output

  • Analog voltage output : 0 ... 10 V DC; 2 ... 10 V DC; 30 mA max.; resolution: 12 mV; Ri ? 330 O (terminal 5+, 6-)

  • Analog current output : 0 ... 20 mA; 4 ... 20 mA; resolution: 25 µA; Ri = 600 O (terminal 4-, 5+)

  • Digital incrementing : = (Ub -3 V), 20 mA, short-circuit proof (Terminals 1-, 2+) 
    with frequency division Fin /1 ... Fin /9999

  • Transfer characteristics

  • Input frequency : = 40000 Hz, pulse pause/pulse length: = 12 µs

  • Deviation : = 0.2 % of full-scale value

  • Standard conformity

  • Electromagnetic compatibility : acc. to EN 50081-2 / EN 50082-2

  • Ambient conditions

  • Ambient temperature : -25 ... 40 °C (-13 ... 104 °F)

  • Storage temperature : -40 ... 85 °C (-40 ... 185 °F)

  • Relative humidity : max. 80 %, not condensing

  • Altitude : 0 ... 2000 m

  • Operating conditions : The device has only to be used in an indoor area.

  • Mechanical specifications

  • Connection assembly : Caution: Please be aware that the device may only be connected to a switchable power supply. The switch or circuit breaker must be easy to reach and identified as the separator for the device.

  • Degree of protection : IP20

  • Connection : coded, removable terminals , max. core cross section 0.34 ... 2.5 mm2

  • Construction type : modular terminal housing in Makrolon, System KF 
    For use in the switch cabinet/switch cabinet module

  • Mounting : snap-on to 35 mm standard rail or screw fixing

  • Shipping Weight : 1.5 Kg