Delta VFDB4030
DELTA VFDB braking units are applied to absorb the motor regeneration energy when the three-phase induction motor stops
by deceleration. With VFDB braking unit, the regeneration energy will be dissipated in dedicated braking resistors.
To prevent mechanical or human injury.
by deceleration. With VFDB braking unit, the regeneration energy will be dissipated in dedicated braking resistors.
To prevent mechanical or human injury.
Yaskawa Braking Unit :-
CDBR-4030, CDBR-4030D,
CDBR-4045, CDBR-4045D
Specification:-
Part Time Rating: 60A x 10 seconds to 10% duty.
Continuous Rating: 18A.
AC Supply Voltage : 380V to 460V.
Trip level: 630V DC to 760V DC, User adjustable in 10 steps via pre-set down from the Default setting of 760V (highest).
More Details...